Responses of a tall building with U.S. code-type instrumentation in Tokyo, Japan, to events before, during and after the Tohoku earthquake of 11 March 2011

November 3, 2016

The 11 March 2011 M 9.0 Tohoku earthquake generated long-duration shaking that propagated hundreds of kilometers from the epicenter and affected tall buildings in urban areas several hundred kilometers from the epicenter of the main shock. Recorded responses show that tall buildings were affected by long-period motions. This study presents the behavior and performance of a 37-story building in the Tsukuda area of Tokyo, Japan, as inferred from modal analyses of records retrieved for a time interval covering a few days before, during, and for several months after the main shock. The U.S. “code-type” array comprises three triaxial accelerometers deployed at three levels in the superstructure. Such a sparse array in a tall structure limits a reliable assessment, because its performance must be based on only the average drift ratios. Based on the inferred values of this parameter, the subject building was not structurally damaged.

Publication Year 2016
Title Responses of a tall building with U.S. code-type instrumentation in Tokyo, Japan, to events before, during and after the Tohoku earthquake of 11 March 2011
DOI 10.1193/052114EQS071M
Authors Mehmet Çelebi, Toshihide Kashima, S. Farid Ghahari, Fariba Abazarsa, Ertugrul Taciroglu
Publication Type Article
Publication Subtype Journal Article
Series Title Earthquake Spectra
Index ID 70178120
Record Source USGS Publications Warehouse
USGS Organization Earthquake Science Center